Rini Ann Jerin A, Kaliannan Palanisamy, Subramaniam Umashankar
School of Electrical Engineering, VIT University, Vellore 632014, Tamil Nadu, India.
ISA Trans. 2017 Sep;70:465-474. doi: 10.1016/j.isatra.2017.06.029. Epub 2017 Jul 6.
Fault ride through (FRT) capability in wind turbines to maintain the grid stability during faults has become mandatory with the increasing grid penetration of wind energy. Doubly fed induction generator based wind turbine (DFIG-WT) is the most popularly utilized type of generator but highly susceptible to the voltage disturbances in grid. Dynamic voltage restorer (DVR) based external FRT capability improvement is considered. Since DVR is capable of providing fast voltage sag mitigation during faults and can maintain the nominal operating conditions for DFIG-WT. The effectiveness of the DVR using Synchronous reference frame (SRF) control is investigated for FRT capability in DFIG-WT during both balanced and unbalanced fault conditions. The operation of DVR is confirmed using time-domain simulation in MATLAB/Simulink using 1.5MW DFIG-WT.
随着风能在电网中的渗透率不断提高,风力涡轮机的故障穿越(FRT)能力以在故障期间维持电网稳定性已成为强制性要求。基于双馈感应发电机的风力涡轮机(DFIG-WT)是最常用的发电机类型,但极易受到电网电压干扰的影响。考虑了基于动态电压恢复器(DVR)的外部FRT能力改进。由于DVR能够在故障期间快速减轻电压跌落,并能维持DFIG-WT的额定运行条件。研究了采用同步参考框架(SRF)控制的DVR在DFIG-WT的平衡和不平衡故障条件下FRT能力的有效性。使用1.5MW DFIG-WT在MATLAB/Simulink中进行时域仿真,验证了DVR的运行情况。