[医院环境中的军团菌污染:对卡塔尼亚(意大利)三家医院热水供应系统的监测]

[Legionella contamination in the hospital environment: monitoring of the hot water distribution systems of three hospitals in Catania (Italy)].

作者信息

Pignato S, Coniglio M A, Faro G, Cantaro P, Carini S A, Mangano G, Cunsolo R, Coco G, Giammanco G

机构信息

Dipartimento G.F. Ingrassia Igiene e Sanità Pubblica, Laboratorio di Riferimento Regionale per le Legionellosi, Università di Catania.

出版信息

Ig Sanita Pubbl. 2006 Nov-Dec;62(6):635-52.

Abstract

This study evaluated the presence and extent of contamination with Legionella spp. in the hot water distribution systems of three hospitals in Catania (Italy). In total, 291 hot water samples were collected between September 2002 and August 2005 and these were examined in order to monitor the hospital distribution systems and evaluate the efficacy of decontamination measures. L. pneumophila was detected at variable concentrations up to over 10000 UFC/L at several collection sites in some hospital buildings and branches of the water distribution system while other buildings/branches were found to be free of contamination. The most frequently isolated serogroup was L. pneumophila serogroup 3, occasionally associated with serogroups 4, 5 and 6. Molecular typing of Legionella strains by pulsed-field gel electrophoresis of genomic DNA restriction fragments identified four different genotypes, each recovered from a different branch of the distribution system. Decontamination procedures, including shock hyperchloration and two different thermal shock methods, performed between October 2003 and August 2005, led to only temporary reductions in contamination. In fact, previous concentrations of the same L. pneumophila serogroup were found within 3 to 8 months of decontamination. In order to prevent and monitor Legionella infections, sterilizing filters were installed in water taps of all wards with high-risk patients and urinary antigen testing was performed on all patients diagnosed with nosocomial pneumonia. No cases of Legionella pneumonia were identified in 2005.

摘要

本研究评估了意大利卡塔尼亚市三家医院热水供应系统中嗜肺军团菌的污染情况及程度。2002年9月至2005年8月期间,共采集了291份热水样本,对这些样本进行检测以监测医院供水系统并评估去污措施的效果。在一些医院建筑和供水系统分支的多个采样点检测到嗜肺军团菌,其浓度各不相同,最高超过10000 UFC/L,而其他建筑/分支未发现污染。最常分离出的血清型是嗜肺军团菌血清型3,偶尔与血清型4、5和6同时出现。通过对基因组DNA限制性片段进行脉冲场凝胶电泳对军团菌菌株进行分子分型,鉴定出四种不同的基因型,每种基因型分别从供水系统的不同分支中分离得到。2003年10月至2005年8月期间采取的去污程序,包括冲击加氯和两种不同的热冲击方法,仅导致污染暂时减少。事实上,在去污后的3至8个月内又发现了之前相同嗜肺军团菌血清型的浓度。为预防和监测军团菌感染,在所有收治高危患者病房的水龙头上安装了除菌过滤器,并对所有诊断为医院获得性肺炎的患者进行了尿抗原检测。2005年未发现军团菌肺炎病例。

文献AI研究员

20分钟写一篇综述,助力文献阅读效率提升50倍。

立即体验

用中文搜PubMed

大模型驱动的PubMed中文搜索引擎

马上搜索

文档翻译

学术文献翻译模型,支持多种主流文档格式。

立即体验