Tekeli Ayça N, Arslan Ayla
Environmental Engineering Department, University of Kocaeli, 41040, Izmit, Kocaeli, Turkey.
Environ Monit Assess. 2008 Mar;138(1-3):191-9. doi: 10.1007/s10661-007-9763-6. Epub 2007 Jun 14.
We investigated conventional characterization of wastewaters of the "Kullar Domestic Wastewater Treatment Plant." In the study of conventional characterization; 23 composite samples, which were taken during 10 months, were used and analysed as COD, BOD5, TKN, NH3-N, SS, VSS, TP, RP, TS, Alkalinity, oil and grease, detergent, chloride parameters. For determine of the plant efficiency, 8 output grab samples were taken. The COD and BOD5 values of influent, respectively, ranging from 37 to 1,056 mg/L and 8 to 140 mg/L in total wastewater. The meanly BOD5/COD ratio was calculated as 0.34 in total wastewaters.