Kim Dong Hoon, Lee Hyung Jong
Department of Pathology, Pohang Hospital, Dongguk University College of Medicine, Pohang, Korea.
J Korean Med Sci. 2008 Feb;23(1):163-5. doi: 10.3346/jkms.2008.23.1.163.
A 27-yr-old postgraduate student was found lying at the floor of an unsealed underground dry area, where a valve-opened empty cylinder of liquid nitrogen (150 L) was connected to a cap-removed empty Dewar-flask (10 L) via a copper infusion tube. No injury was found externally or internally. There were petechiae in the bilateral conjunctivae and periorbital skin. The dry area, measuring 300 x 130 x 260 cm, had a communication to the basement of the research building by a window measuring 90 x 60 cm in size at 130 cm above the floor. The scene reconstruction and atmosphere gas analysis revealed that the O2 concentration at 60 cm above the base dropped to 12.0% in 3 min and 10 sec, 10.0% in 8 min and 53 sec, 6.0% in 18 min and 40 sec, and 4.2% in 20 min and 28 sec. The primary cause of death was asphyxia by evaporated liquid nitrogen.
一名27岁的研究生被发现躺在一个未密封的地下干燥区域的地面上,在那里一个阀门打开的空液氮钢瓶(150升)通过一根铜输液管与一个去掉盖子的空杜瓦瓶(10升)相连。体表及体内均未发现损伤。双侧结膜及眶周皮肤有瘀点。该干燥区域尺寸为300×130×260厘米,通过地面上方130厘米处一个尺寸为90×60厘米的窗户与研究楼地下室相通。现场重建及空气气体分析显示,底部上方60厘米处的氧气浓度在3分10秒时降至12.0%,8分53秒时降至10.0%,18分40秒时降至6.0%,20分28秒时降至4.2%。死亡的主要原因是液氮蒸发导致的窒息。