[米兰两家医院对嗜肺军团菌的5年监测及消毒方法比较]

[5-year surveillance for Legionella pneumophila and comparison of disinfection methods in two hospitals of Milan].

作者信息

Galli M G, Tesauro M, Bianchi A, Pregliasco F, Consonni M

机构信息

Dipartimento di Sanità Pubblica, Microbiologia e Virologia, Università degli Studi di Milano.

出版信息

Ann Ig. 2007 Nov-Dec;19(6):533-40.

Abstract

We performed an environmental monitoring in an hospital to estimate the level of contamination from Legionella spp., in connection with several treatments of reclamation. In period 2002-2006 we executed 238 samplings in 21 units hospitals (from hot water, biofilm, filter of the conditioning system, instrument for the assisted respiration) for the detection of Legionella spp. The contaminated points have been subordinates to reclamation (hyperchlorination, maintenance of boilers/tanks, taps' and showers' substitution, increased temperature, elimination of dead points of the system and chlorine dioxide) and subsequently we sampled to verify the efficiency of the disinfection. Environmental investigation found 58% of the cases positive for Legionella spp. (139/238), with maximum count in order of the 10(4) UFC/L, demonstrating colonization of Legionella pneumophila (132/139, 70% Serogroup 2-14, 19% Serogroup 1, 11% both). The used treatments were effective, in different ways, in the short period, but not in the medium-term, because progressive recolonization happened approximately after a month; only the use of chlorine dioxide brought to counts less than 100 UFC/L until now. Chlorine dioxide seems to maintain a mainly protecting effect, however this effectiveness will have to be demonstrated also for longer periods.

摘要

我们在一家医院进行了环境监测,以评估军团菌属的污染水平,并与几种回收处理方法相关联。在2002年至2006年期间,我们在21家医院的科室(从热水、生物膜、空调系统过滤器、辅助呼吸仪器)进行了238次采样,以检测军团菌属。污染点已进行回收处理(超氯化、锅炉/水箱维护、更换水龙头和淋浴喷头、提高温度、消除系统死点和使用二氧化氯),随后我们再次采样以验证消毒效果。环境调查发现58%的病例军团菌属呈阳性(139/238),最高计数为10⁴ UFC/L,表明嗜肺军团菌存在定植(132/139,70%为血清型2 - 14,19%为血清型1,11%为两者兼有)。所采用的处理方法在短期内以不同方式有效,但在中期无效,因为大约一个月后会逐渐重新定植;到目前为止,只有使用二氧化氯使计数低于100 UFC/L。二氧化氯似乎主要起到保护作用,然而这种有效性还需要在更长时间内得到证明。

相似文献

3
Persistence of chlorine-sensitive Legionella pneumophila in hyperchlorinated installations.
J Appl Microbiol. 2008 Sep;105(3):837-47. doi: 10.1111/j.1365-2672.2008.03804.x. Epub 2008 Jun 14.
6
Control of Legionella contamination in a hospital water distribution system by monochloramine.
Am J Infect Control. 2012 Apr;40(3):279-81. doi: 10.1016/j.ajic.2011.03.008. Epub 2011 Jul 8.
8
Disinfection of water distribution systems for Legionella.
Semin Respir Infect. 1998 Jun;13(2):147-59.

文献AI研究员

20分钟写一篇综述,助力文献阅读效率提升50倍。

立即体验

用中文搜PubMed

大模型驱动的PubMed中文搜索引擎

马上搜索

文档翻译

学术文献翻译模型,支持多种主流文档格式。

立即体验