Ding Ming, Zhu Qianlong
Anhui New Energy Utilization and Energy Saving Laboratory, Hefei University of Technology, No. 193 Tunxi Road, Baohe District, Hefei, 230009 Anhui Province China.
Springerplus. 2016 Nov 29;5(1):2037. doi: 10.1186/s40064-016-3700-5. eCollection 2016.
Hardware protection and control action are two kinds of low voltage ride-through technical proposals widely used in a permanent magnet synchronous generator (PMSG). This paper proposes an innovative clustering concept for the equivalent modeling of a PMSG-based wind power plant (WPP), in which the impacts of both the chopper protection and the coordinated control of active and reactive powers are taken into account. First, the post-fault DC link voltage is selected as a concentrated expression of unit parameters, incoming wind and electrical distance to a fault point to reflect the transient characteristics of PMSGs. Next, we provide an effective method for calculating the post-fault DC link voltage based on the pre-fault wind energy and the terminal voltage dip. Third, PMSGs are divided into groups by analyzing the calculated DC link voltages without any clustering algorithm. Finally, PMSGs of the same group are equivalent as one rescaled PMSG to realize the transient equivalent modeling of the PMSG-based WPP. Using the DIgSILENT PowerFactory simulation platform, the efficiency and accuracy of the proposed equivalent model are tested against the traditional equivalent WPP and the detailed WPP. The simulation results show the proposed equivalent model can be used to analyze the offline electromechanical transients in power systems.
硬件保护和控制动作是永磁同步发电机(PMSG)中广泛应用的两种低电压穿越技术方案。本文针对基于PMSG的风电场(WPP)等效建模提出了一种创新的聚类概念,其中考虑了斩波器保护以及有功和无功功率协调控制的影响。首先,选择故障后直流母线电压作为机组参数、来风情况以及到故障点电气距离的集中体现,以反映PMSG的暂态特性。其次,基于故障前风能和端电压跌落,给出了一种计算故障后直流母线电压的有效方法。第三,通过分析计算得到的直流母线电压对PMSG进行分组,无需任何聚类算法。最后,将同一组的PMSG等效为一个重新缩放的PMSG,以实现基于PMSG的WPP的暂态等效建模。利用DIgSILENT PowerFactory仿真平台,将所提等效模型与传统等效WPP和详细WPP进行对比,测试了其效率和准确性。仿真结果表明,所提等效模型可用于分析电力系统中的离线机电暂态。