Radon-222 and 222Rn progeny concentrations measured in an energy-efficient house equipped with a heat exchanger.

作者信息

Holub R F, Droullard R F, Borak T B, Inkret W C, Morse J G, Baxter J F

出版信息

Health Phys. 1985 Aug;49(2):267-77. doi: 10.1097/00004032-198508000-00007.

Abstract

Radon-222 and 222Rn progeny concentrations, barometric pressure and pressure differentials between inside and outside were measured continuously in the basement of a recently constructed energy-efficient house in metropolitan Denver, CO. Although the monitoring equipment was developed primarily for underground mines, it proved to be applicable for house monitoring. Results indicate that for tightly sealed houses, forced-flow transport does not significantly contribute to the 222Rn present even when the pressure within the house is less than the outside pressure by 0.8 Pa (.006 mm Hg). Calculations of 222Rn levels using diffusion as the primary transport mechanism are in agreement with observed data. The diffusion coefficient of 222Rn in the walls and floor surrounding the basement is higher than values previously reported. Ventilation by means of a heat exchanger reduces the 222Rn levels in accordance with measured air exchange rates, regardless of the pressure differential between inside and outside.