Triantafyllidou Simoni, Lytle Darren, Chen Abraham S C, Wang Lili, Muhlen Christy, Sorg Thomas J
US Environmental Protection Agency, Office of Research and Development, Cincinnati, OH.
ALSA Tech, North Potomac, MD.
AWWA Water Sci. 2019 Aug 13;1(4). doi: 10.1002/aws2.1149.
Retrospective analysis of 20 water systems from the USEPA's Arsenic Demonstration Program revealed three patterns of arsenic levels at the tap, after arsenic treatment of the source well water. Following an initial destabilization period, Pattern A systems (6/20 with low iron/manganese in source water and plastic piping) had arsenic concentrations that did not change as water traveled to consumer taps (conservative contaminant behavior). Pattern B systems (8/20 with high iron/manganese in source water and iron piping) had consistently higher arsenic concentrations at consumer taps, above the arsenic content of incoming treated water, for months to more than a year after arsenic treatment (non-conservative behavior). Pattern C systems (6/20 with additional occasional arsenic treatment complications) experienced multiple arsenic spikes at consumer taps (non-conservative and unpredictable behavior). These field observations suggest that in some water distribution systems arsenic may linger long after it has been removed at its source.
对美国环境保护局(USEPA)砷示范项目中的20个供水系统进行回顾性分析发现,在对源井水进行砷处理后,水龙头处的砷含量呈现出三种模式。在经历初始的不稳定期后,模式A系统(源水中铁/锰含量低且采用塑料管道的20个系统中的6个)在水输送到用户水龙头的过程中砷浓度没有变化(污染物行为保守)。模式B系统(源水中铁/锰含量高且采用铁管道的20个系统中的8个)在砷处理后的数月至一年多时间里,用户水龙头处的砷浓度始终高于处理后进入的水中的砷含量(行为不保守)。模式C系统(20个系统中的6个,存在额外的偶尔砷处理并发症)在用户水龙头处出现多次砷含量峰值(行为不保守且不可预测)。这些实地观察结果表明,在一些供水系统中,砷在水源处被去除后可能会长期留存。