Stano Ernest, Kaczmarek Michal
Institute of Mechatronics and Information Systems, Lodz University of Technology, Stefanowskiego 18/22 St, 90-924 Lodz, Poland.
Sensors (Basel). 2020 Apr 11;20(8):2167. doi: 10.3390/s20082167.
Self-calibration of a designed wideband inductive current transformer (CT) was carried out in the ampere-turns condition. This method does not require a reference transducer. The values of current and phase errors at the harmonics of frequencies from 100 Hz to 5 kHz were determined for the distorted primary current of the rated main frequency equal to 50 Hz. These results were verified based on the comparison of values measured between two CTs and calculated as the difference between values obtained from their calibration. Moreover, from vectorial diagrams drawn for transformation of the higher harmonics, the source of the change in the values of current and phase errors with frequency is explained. Furthermore, the method for calculation of the values of the corresponding harmonics of the current associated with the active power losses in the core and the magnetization current is presented.
在安匝数条件下对设计的宽带感应电流互感器(CT)进行了自校准。该方法不需要参考传感器。对于额定基频为50Hz的畸变一次电流,确定了100Hz至5kHz频率谐波处的电流值和相位误差。通过比较两个CT之间测量的值,并将其计算为校准所得值之间的差值,对这些结果进行了验证。此外,从为高次谐波变换绘制的矢量图中,解释了电流值和相位误差随频率变化的来源。此外,还提出了计算与铁芯中的有功功率损耗和磁化电流相关的电流相应谐波值的方法。