City of Vancouver, Development, Buildings & Licensing, 515 W 10th Avenue, Vancouver, BC V5Z 4A8, Canada E-mail:
J Water Health. 2023 Mar;21(3):313-328. doi: 10.2166/wh.2023.154.
Cooling towers have been linked to Legionnaires' disease cases and outbreaks. Legionella pneumophila results (from a culture-based method) are presented for 557 cooling towers across the City of Vancouver, Canada for 2021. Results of 10 CFU/mL or greater (defined as exceedances) were reported for 30 cooling towers (5.4%), including six >1,000 CFU/mL, and L. pneumophila serogroup 1 (sg1) was identified in 17 of these cooling towers (out of 28 with serogroup-level analysis). The data indicate highly localised Legionella issues, with exceedances concentrated within 16 facilities, including two hospitals. In the 3 months preceding each cooling tower exceedance, the nearest municipal water sampling station had a free chlorine residual of at least 0.46 mg/L and a temperature of <20 °C. There was not a statistically significant correlation between the L. pneumophila concentration of a cooling tower in exceedance and the municipal water free chlorine residual, temperature, pH, turbidity or conductivity. There was a statistically significant negative correlation between the concentrations of L. pneumophila sg1 and other L. pneumophila serogroups in cooling towers. This unique dataset underscores the pivotal role of building owners and managers in preventing the growth of Legionella bacteria and the value of regulations to verify operations and maintenance practices.
冷却塔与军团病病例和疫情有关。2021 年,加拿大温哥华市对 557 座冷却塔进行了嗜肺军团菌检测(基于培养法)。结果显示,有 30 座冷却塔(5.4%)的结果超过了 10CFU/mL(定义为超标),其中 6 座超过了 1000CFU/mL,在这些冷却塔中,有 17 座(占进行血清群水平分析的 28 座冷却塔中的 17 座)检测到嗜肺军团菌血清群 1(sg1)。数据表明存在高度局部化的军团菌问题,超标集中在 16 个设施内,包括两家医院。在每个冷却塔超标前的 3 个月内,最近的市政水样采集站的余氯含量至少为 0.46mg/L,温度低于 20°C。在超标冷却塔中的嗜肺军团菌浓度与市政水中余氯含量、温度、pH 值、浊度或电导率之间没有统计学上的显著相关性。在超标冷却塔中,嗜肺军团菌 sg1 浓度与其他嗜肺军团菌血清群之间存在统计学上的显著负相关。这个独特的数据集强调了建筑物所有者和管理者在防止军团菌生长方面的关键作用,以及法规在验证操作和维护实践方面的价值。