Legionella in Primary School Hot Water Systems from Two Municipalities in the Danish Capital Region.

作者信息

Nielsen Niss Skov, Fojan Peter, Jensen Rasmus Lund, Wahedi Haseebullah, Afshari Alireza

机构信息

Division of Building Technology, Management and Indoor Environment, Danish Building Research Institute (Build), Aalborg University, A.C. Meyers Vaenge 15, 2450 Copenhagen, Denmark.

Centre for Health Research, Zealand University Hospital, Strandboulevarden 64, 4800 Nykøbing Falster, Denmark.

出版信息

Microorganisms. 2024 Oct 16;12(10):2074. doi: 10.3390/microorganisms12102074.

Abstract

Legionella contamination in public water systems poses significant health risks, particularly in schools where vulnerable populations, including children, regularly use these facilities. This study investigates the presence of Legionella in the hot water systems from 49 primary schools across two municipalities in the Danish capital region. Water samples were collected from taps in each school, and both first-flush and stabile temperature samples were analysed for Legionella contents. The findings revealed that 97% of schools in Municipality 1 and 100% in Municipality 2 had Legionella in their hot water systems. The content of Legionella colonies was significantly higher in schools in Municipality 1, which was probably because of overall lower water temperatures. At stabile temperatures, 76% and 50% of the schools in the two municipalities exceeded the European Union's recommended limit of 1000 CFU/L. Stabile peripheral water temperatures were achieved after 3 min. Tap water temperatures above 54 °C and central tank temperatures above 59 °C were associated with Legionella contents below 1000 CFU/L. This study highlights the need for more stringent Legionella control procedures in schools, including higher water temperatures and refining Legionella reducing interventions with the addition of regular flow and draining procedures.

摘要

公共供水系统中的军团菌污染会带来重大健康风险,尤其是在学校,包括儿童在内的弱势群体经常使用这些设施。本研究调查了丹麦首都地区两个市的49所小学热水系统中军团菌的存在情况。从每所学校的水龙头采集水样,对首次冲洗水样和稳定温度水样都进行了军团菌含量分析。研究结果显示,市1中97%的学校以及市2中100%的学校热水系统中存在军团菌。市1学校中军团菌菌落含量显著更高,这可能是因为总体水温较低。在稳定温度下,两个市分别有76%和50%的学校超过了欧盟建议的1000 CFU/L的限值。3分钟后达到稳定的外周水温。自来水温度高于54°C以及中央水箱温度高于59°C时,军团菌含量低于1000 CFU/L。本研究强调学校需要采取更严格的军团菌控制程序,包括提高水温,以及通过增加定期的流水和排水程序来优化减少军团菌的干预措施。

https://cdn.ncbi.nlm.nih.gov/pmc/blobs/93b1/11510371/b5fd00a2d1f2/microorganisms-12-02074-g001.jpg

文献AI研究员

20分钟写一篇综述,助力文献阅读效率提升50倍。

立即体验

用中文搜PubMed

大模型驱动的PubMed中文搜索引擎

马上搜索

文档翻译

学术文献翻译模型,支持多种主流文档格式。

立即体验