Simard C, Trudel M, Paquette G, Payment P
J Hyg (Lond). 1983 Oct;91(2):277-86. doi: 10.1017/s0022172400060290.
The microbial and viral flora in the ventilating ducts of an apartment building was evaluated. Several types of sampler (slit sampler, Andersen sampler, large volume air sampler) were used to evaluate the hourly, weekly and seasonal variation of this flora. The mean bacterial concentration was 17.2 e.f.u./m3 with a maximum level at 07.30 h (41.3 c.f.u./m3) and a minimal concentration in the early afternoon (8 c.f.u./m3). The bacterial concentration observed correlated with the relative humidity in the air-ducts although there were no seasonal differences. The bacteria were mainly gram-positive cocci (73.5%) represented by a large number of Micrococcaceae (47.1%); gram-positive bacilli accounted for 14.2% of the isolates, gram-negative bacilli 12.0% and gram-negative cocci 0.3%. The majority of the bacteria-carrying particles were in the respirable range with 80.4% of them being less than 5 microns. The methods used did not result in the isolation of viruses during the winter sampling period.
对一栋公寓楼通风管道中的微生物和病毒菌群进行了评估。使用了几种类型的采样器(狭缝采样器、安德森采样器、大容量空气采样器)来评估该菌群的每小时、每周和季节性变化。细菌平均浓度为17.2 e.f.u./m³,在07:30时达到最高水平(41.3 c.f.u./m³),下午早些时候浓度最低(8 c.f.u./m³)。尽管没有季节性差异,但观察到的细菌浓度与风道中的相对湿度相关。细菌主要为革兰氏阳性球菌(73.5%),其中大量为微球菌科(47.1%);革兰氏阳性杆菌占分离菌的14.2%,革兰氏阴性杆菌占12.0%,革兰氏阴性球菌占0.3%。大多数携带细菌的颗粒在可吸入范围内,其中80.4%小于5微米。在冬季采样期间,所使用的方法未分离出病毒。