Xuan Jing, Pan Xingfu, Liu Xiaodong, Yan Huifang, Zhang Yanshu
School of Public Health, Hebei United University, Tangshan 063000, China.
E-mail:
Zhonghua Lao Dong Wei Sheng Zhi Ye Bing Za Zhi. 2015 Feb;33(2):143-5.
To establish a method for determination of N-isopropylaniline in the workplace atmosphere by gas chromatography.
Air samples were collected by silica gel tube and desorbed by acetone. Then they were separated through DB-WAX columns and N-isopropylaniline was determined by flame ionization detector.
The concentration of N-isopropylaniline showed a good linear relationship within the range of 1.40∼665.0 µg/ml. The sampling efficiency was 100%. The accuracy was 96%∼ 99% and the precision was 2.1%∼7.0%. The minimum detectable concentration was 0.056 mg/m(3) (with sampled air volume of 7.5 L).
The method meets the requirements of analysis and applies to the determination of N-isopropylaniline in the workplace atmosphere.