Suppr超能文献

希腊旅游胜地酒店水系统中的军团菌定植:与系统特征和理化参数的关联。

Legionella Colonization of Hotel Water Systems in Touristic Places of Greece: Association with System Characteristics and Physicochemical Parameters.

机构信息

Department of Hygiene and Epidemiology, Medical School, University of Thessaly, 41222 Larissa, Greece.

Regional Public Health Laboratory of Thessaly, 41222 Larissa, Greece.

出版信息

Int J Environ Res Public Health. 2018 Nov 30;15(12):2707. doi: 10.3390/ijerph15122707.

Abstract

This study aimed to assess the colonization of hotel water systems in central Greece and Corfu by , and to investigate the association between physicochemical parameters and colonization. Standardized hygiene inspection was conducted in 51 hotels, and 556 water samples were analyzed for spp Free chlorine concentration, pH, hardness, conductivity, and trace metals were defined in cold water samples. The results of inspections and chemical analyses were associated with the microbiological results using univariate and logistic regression analysis. According to the score of the checklist used for the inspections, 17.6% of the hotels were classified as satisfactory, 15.7% as adequate, and 66.7% as unsatisfactory. Moreover, 74.5% of the hotels were colonized by spp. and 31.4% required remedial measures according to the European guidelines. spp were isolated in 28% of the samples. Unsatisfactory results of inspections were associated with presence (relative risk (RR) = 7.67, -value = 0.043). In hot-water systems, <50 °C temperatures increased the risk of colonization (RR = 5.36, -value < 0.001). In cold-water systems, free chlorine concentration <0.375 mg/L (odds ratio (OR) = 9.76, -value = 0.001), pH ≥ 7.45 (OR = 4.05, -value = 0.007), and hardness ≥321 mgCaCO₃/L (OR = 5.63, -value = 0.003) increased the risk, whereas copper pipes demonstrated a protective role (OR = 0.29, -value = 0.0024). The majority of the hotels inspected were colonized with . Supplementary monitoring of the risk factors that were identified should be considered.

摘要

本研究旨在评估希腊中部和科孚岛酒店水系统中 的定植情况,并调查理化参数与 定植之间的关联。对 51 家酒店进行了标准化卫生检查,对 556 个水样进行了分析,以检测 spp。在冷水中测定游离氯浓度、pH 值、硬度、电导率和痕量金属。使用单变量和逻辑回归分析将检查和化学分析的结果与微生物学结果相关联。根据检查表的得分,17.6%的酒店被归类为满意,15.7%为充分,66.7%为不满意。此外,74.5%的酒店被 spp 定植,根据欧洲指南,31.4%需要采取补救措施。28%的样本中分离出 spp。检查结果不理想与 定植有关(相对风险 (RR) = 7.67,-值 = 0.043)。在热水系统中,<50°C 的温度增加了 定植的风险(RR = 5.36,-值 < 0.001)。在冷水系统中,游离氯浓度 <0.375 mg/L(比值比 (OR) = 9.76,-值 = 0.001)、pH 值≥7.45(OR = 4.05,-值 = 0.007)和硬度≥321 mgCaCO₃/L(OR = 5.63,-值 = 0.003)增加了风险,而铜管则起到了保护作用(OR = 0.29,-值 = 0.0024)。检查的大多数酒店都定植了 。应考虑对确定的危险因素进行补充监测。

https://cdn.ncbi.nlm.nih.gov/pmc/blobs/ad6a/6313630/ab9b750bb508/ijerph-15-02707-g001.jpg

文献AI研究员

20分钟写一篇综述,助力文献阅读效率提升50倍。

立即体验

用中文搜PubMed

大模型驱动的PubMed中文搜索引擎

马上搜索

文档翻译

学术文献翻译模型,支持多种主流文档格式。

立即体验