[The use of UV rays for the disinfection of water. I. Microbiologic studies of drinking water].

作者信息

Martiny H, Wlodavezyk K, Harms G, Rüden H

机构信息

Fachgebiet Hygiene der Technischen Universität Berlin.

出版信息

Zentralbl Bakteriol Mikrobiol Hyg B Umwelthyg Krankenhaushyg Arbeitshyg Prav Med. 1988 Jan;185(4-5):350-67.

PMID:3131986
Abstract

As a physical disinfection method without chemicals required the ultraviolet irradiation was tested for disinfection of drinking water. The survival was measured as a function of exposure to radiation for S. enteritidis, E. cloacae, C. freundii, S. marcescens, E. coli, K. pneumoniae und S. faecium. The bacteria were grown in trypton soya broth until they were well into the exponential phase. Two different UV-disinfection units were tested. Both consist of cylindrical shaped chambers with one low-pressure mercury-discharge lamp with their longitudinal axis parallel to the chambers. With 10(6) cfu/ml the experiments were done with three different rates of flow of 7,2 m3/h, 4,0 m3/h and 2,0 m3/h. The minimum exposures to radiation necessary to cause a 99.999% reduction were 10-86 mWs/cm2 depending on the test bacterium and on the UV-disinfection unit. The minimum doses ranged for S. enteritidis up to 13 mWs/cm2, for E. coli up to 21 mWs/cm2, for K. pneumoniae up to 39 mWs/cm2, for S. faecium up to 42 mWs/cm2, for E. cloacae up to 43 mWs/cm2, for C. freundii up to 72 mWs/cm2, and for S. marcescens up to 86 mWs/cm2.