The acoustic signal in the operation of a power transformer contains a lot of transformer operation state information, which is of great significance to the detection of DC bias state. In this paper, three typical parameters used for DC bias state detection are selected by comparing the acoustic variation of a 500 kV Jingting transformer substation No. 2 transformer with that of the core model built in the laboratory; then, acoustic samples of the 162 EHV normal state transformers are collected, and the distribution regularity of three typical parameters in normal state is given. Finally, according to the distribution regularity, clear warning threshold of typical parameters are given, and the DC bias cases from the 500 kV Jingting transformer substation are used to verify the effectiveness of the threshold.
电力变压器运行中的声信号包含大量变压器运行状态信息,对检测直流偏磁状态具有重要意义。本文通过对比实验室建立的铁心模型与 500kV 荆亭变电站 2 号主变的声变化,选择了三种用于检测直流偏磁状态的典型参数;然后,采集了 162 台特高压正常状态的变压器的声样本,给出了三种典型参数在正常状态下的分布规律。最后,根据分布规律,给出了典型参数的明确预警阈值,并利用 500kV 荆亭变电站的直流偏磁案例验证了阈值的有效性。