Suppr超能文献

三种烟雾探测器推广计划的评估。

Evaluation of three smoke detector promotion programs.

作者信息

Shults R A, Sacks J J, Briske L A, Dickey P H, Kinde M R, Mallonee S, Douglas M R

机构信息

National Center for Injury Prevention and Control, Centers for Disease Control and Prevention (CDC), Atlanta, Georgia 30341-3724, USA.

出版信息

Am J Prev Med. 1998 Oct;15(3):165-71. doi: 10.1016/s0749-3797(98)00071-3.

Abstract

CONTEXT

Seventy percent of U.S. residential fire deaths occur in homes without a working smoke detector. To help prevent residential fire deaths, many programs have distributed or installed detectors in unprotected homes. Because persons receiving a detector may not install it and because detector batteries require annual replacement, the enduring effectiveness of these programs may be questioned.

OBJECTIVE

We evaluated the long-term functional status of smoke detectors distributed to high-risk households in eight areas of Minnesota, Cherokee County (North Carolina), and Oklahoma City (Oklahoma).

DESIGN

Cross-sectional.

SETTING

Home visits were made to check the detectors that were distributed 3 to 4 years earlier.

PARTICIPANTS

Randomly selected households from the three detector promotion programs. MAIN OUT-COME MEASURE: At least one working smoke detector.

RESULTS

Participation rates ranged from 72% to 82%. The percentage of evaluation households with at least one working detector ranged from 58% in Oklahoma to 73% in North Carolina. In 76% of households with nonworking detectors, the batteries were either missing or disconnected. When batteries in nonworking detectors were replaced, 83% of the detectors regained function.

CONCLUSIONS

Future programs should consider distributing detectors that do not require annual battery changes or find effective ways to ensure that batteries are routinely replaced. Programs should also provide each household with the number of detectors needed to meet the most current recommended standard of the National Fire Protection Agency. The evaluation's participation rates support the practicality of unannounced home visits to evaluate home injury prevention programs in high-risk groups.

摘要

背景

美国70%的住宅火灾死亡事件发生在没有正常工作的烟雾探测器的家庭中。为帮助预防住宅火灾死亡,许多项目已在未受保护的家庭中分发或安装了探测器。由于收到探测器的人可能不会安装,且探测器电池需要每年更换,这些项目的持久有效性可能受到质疑。

目的

我们评估了分发给明尼苏达州八个地区、北卡罗来纳州切诺基县和俄克拉何马城(俄克拉何马州)高危家庭的烟雾探测器的长期功能状态。

设计

横断面研究。

地点

进行家访以检查3至4年前分发的探测器。

参与者

从三个探测器推广项目中随机选择的家庭。主要结局指标:至少有一个正常工作的烟雾探测器。

结果

参与率在72%至82%之间。有至少一个正常工作探测器的评估家庭百分比在俄克拉何马州为58%,在北卡罗来纳州为73%。在探测器不工作的家庭中,76%的电池缺失或未连接。当为不工作探测器更换电池后,83%的探测器恢复了功能。

结论

未来的项目应考虑分发无需每年更换电池的探测器,或找到确保电池定期更换的有效方法。项目还应为每个家庭提供符合美国国家消防协会最新推荐标准所需数量 的探测器。评估的参与率支持了对高危群体家庭伤害预防项目进行不事先通知的家访的实用性。