Turk B H, Prill R J, Fisk W J, Grimsrud D T, Sextro R G
Indoor Environment Program, Lawrence Berkeley Laboratory, Berkeley, California.
J Air Waste Manage Assoc. 1991 May;41(5):723-34. doi: 10.1080/10473289.1991.10466873.
Radon control systems were installed and evaluated in fourteen homes in the Spokane River Valley/Rathdrum Prairie and in one home in Vancouver, Washington. Because of local soil conditions, subsurface ventilation (SSV) by pressurization was always more effective in these houses than SSV by depressurization in reducing indoor radon levels to below guidelines. Basement overpressurization was successfully applied in five houses with airtight basements where practical-sized fans could develop an overpressure of 1 to 3 Pascals. Crawlspace ventilation was more effective than crawlspace isolation in reducing radon entry from the crawlspace, but had to be used in conjunction with other mitigation techniques, since the houses also had basements. Indoor radon concentrations in two houses with air-to-air heat exchangers (AAHX) were reduced to levels inversely dependent on the new total ventilation rates and were lowered even further in one house where the air distribution system was modified. Sealing penetrations in the below-grade surfaces of substructures was relatively ineffective in controlling radon. Operation of the radon control systems (except for the AAHX's) made no measureable change in ventilation rates or indoor concentrations of other measured pollutants. Installation costs by treated floor area ranged from approximately $4/m2 for sealing to $28/m2 for the AAHX's. Based on the low electric rates for the region, annual operating costs for the active systems were estimated to be approximately $60 to $170.
在斯波坎河谷/拉思德拉姆草原的14所房屋以及华盛顿州温哥华的1所房屋中安装并评估了氡控制系统。由于当地土壤条件,在这些房屋中,通过增压进行的地下通风(SSV)在将室内氡水平降低至指导标准以下方面始终比通过减压进行的SSV更有效。地下室过压成功应用于5所地下室气密的房屋,在这些房屋中,实际尺寸的风扇可以产生1至3帕斯卡的过压。在减少来自爬行空间的氡进入方面,爬行空间通风比爬行空间隔离更有效,但由于这些房屋也有地下室,因此必须与其他缓解技术结合使用。两所装有空气对空气热交换器(AAHX)的房屋中的室内氡浓度降低到与新的总通风率成反比的水平,并且在一所修改了空气分配系统的房屋中甚至进一步降低。在控制氡方面,密封下部结构地下表面的贯穿孔相对无效。氡控制系统(除AAHX外)的运行对通风率或其他测量污染物的室内浓度没有可测量的变化。按处理后的地板面积计算,安装成本从密封的约4美元/平方米到AAHX的28美元/平方米不等。根据该地区的低电价,有源系统的年度运行成本估计约为60至170美元。