Cho Wan-Ho, Jeong Cheol-Ho, Chang Ji-Ho, Lee Seong-Hyun, Park Moo Kyun, Suh Myung-Whan, Han Jae Joon
Division of Physical Metrology, Korea Research Institute of Standards and Science, Daejeon, Korea.
Acoustic Technology, Electrical Engineering Department, Technical University of Denmark, Lyngby, Denmark.
J Audiol Otol. 2019 Apr;23(2):76-82. doi: 10.7874/jao.2018.00269. Epub 2019 Apr 10.
Noise levels and room acoustic parameters at a tertiary referral hospital, Seoul National University Hospital (SNUH) in Korea, are investigated.
Through a questionnaire, acoustically problematic rooms are identified. Noise levels in emergency rooms (ERs) and intensive care units (ICUs) are measured over about three days. Acoustically critical and problematic rooms in the otolaryngology department are measured including examination rooms, operating rooms, nurse stations, receptions, and patient rooms.
The A-weighted equivalent noise level, LAeq, ranges from 54 to 56 dBA, which is at least 10 dB lower than the noise levels of 65 to 73 dBA measured in American ERs. In an ICU, the noise level for the first night was 66 dBA, which came down to 56 dBA for the next day. The noise levels during three different ear surgeries vary from 57 to 62 dBA, depending on the use of surgical drills and suctions. The noise levels in a patient room is found to be 47 dBA, while the nurse stations and the receptions have high noise levels up to 64 dBA. The reverberation times in an operation room, examination room, and single patient room are found to be below 0.6 s.
At SNUH, the nurse stations and receptions were found to be quite noisy. The ERs were quieter than in the previous studies. The measured reverberation times seemed low enough but some other nurse stations and examination rooms were not satisfactory according to the questionnaire.
对韩国首尔国立大学医院(SNUH)这家三级转诊医院的噪声水平和室内声学参数进行了调查。
通过问卷调查,确定声学上存在问题的房间。在大约三天的时间里测量急诊室(ER)和重症监护病房(ICU)的噪声水平。对耳鼻喉科声学关键和存在问题的房间进行测量,包括检查室、手术室、护士站、接待处和病房。
A加权等效噪声级LAeq范围为54至56 dBA,比美国急诊室测量的65至73 dBA的噪声水平至少低10 dB。在一个重症监护病房,第一晚的噪声水平为66 dBA,第二天降至56 dBA。三种不同耳部手术期间的噪声水平根据手术钻头和吸引器的使用情况在57至62 dBA之间变化。发现病房的噪声水平为47 dBA,而护士站和接待处的噪声水平高达64 dBA。发现手术室、检查室和单人病房的混响时间低于0.6秒。
在首尔国立大学医院,发现护士站和接待处相当嘈杂。急诊室比以前的研究中更安静。测量的混响时间似乎足够低,但根据问卷调查,其他一些护士站和检查室并不令人满意。