Occurrence and parameters of frequency of Legionella in warm water systems of hospitals and hotels in Lower Saxony.

作者信息

Habicht W, Müller H E

机构信息

Staatlichen Medizinaluntersuchungsamt Braunschweig.

出版信息

Zentralbl Bakteriol Mikrobiol Hyg B Umwelthyg Krankenhaushyg Arbeitshyg Prav Med. 1988 Mar;186(1):79-88.

PMID:3134774
Abstract

A total of 1241 water samples was investigated from 103 hospitals and 62 hotels in Lower Saxony 1985-87. 331 of 949 samples from hospitals and 26 of 292 samples from hotels were Legionella positive. All together 70% of the hospitals and 18% of the hotels investigated were Legionella positive, and 836 strains of Legionella were isolated (Table 1). As they could be diagnosed they belong to L. pneumophila SG1 306 strains, SG2 36 strains, SG3 127 strains, SG4 45 strain, SG5 29 strain, SG6 106 strains, SG9 13 strains and SG10 13 strains. Further 134 strains belonging to L. pneumophila but not to SG1-SG12 show cross reactions with serogroups 5, 8, and 10. Finally, 16 strains belong to L. dumoffii and 1 strain to L. anisa (Table 2). The following parameters of water samples were studied, too: temperature, pH value, conductivity, concentration of iron, of organic matter, of other bacteria, occurrence of amoebas, and the materials of water plumbing systems. Most samples contained concentrations of Legionella in the range of 10(1)-10(3) CFU/ml, highest concentrations were 10(5) CFU/ml (Fig. 1). Most frequently, Legionella were isolated within the range of temperature of 35-45 degrees C. However, a few of the water samples were positive for Legionella even up to 66 degrees C (Fig. 3). The conductivity has no and the pH value (Fig. 2) has only little influence on the occurrence of Legionella. There is a positive correlation between concentration of iron and frequency of Legionella (Fig. 4). Also organic matter (Fig. 6) and amoebas (Table 3) seem to enhance the occurrence of Legionella. Plumbing systems consisting of copper showed an inhibitory effect on Legionella during the first five years, whereas no effect could be detected in older systems (Fig. 5).

摘要

1985 - 1987年期间,对下萨克森州103家医院和62家酒店的共计1241份水样进行了调查。医院的949份样本中有331份、酒店的292份样本中有26份军团菌检测呈阳性。总计,被调查的医院中有70%、酒店中有18%军团菌检测呈阳性,共分离出836株军团菌(表1)。经诊断,它们分别属于嗜肺军团菌血清1型306株、血清2型36株、血清3型127株、血清4型45株、血清5型29株、血清6型106株、血清9型13株和血清10型13株。另外,134株属于嗜肺军团菌但不属于血清1 - 12型的菌株与血清5型、8型和10型有交叉反应。最后,16株属于杜莫夫军团菌,1株属于阿尼萨军团菌(表2)。还研究了水样的以下参数:温度、pH值、电导率、铁浓度、有机物浓度、其他细菌浓度、变形虫的存在情况以及供水管道系统的材料。大多数样本中军团菌的浓度在10¹ - 10³CFU/ml范围内,最高浓度为10⁵CFU/ml(图1)。军团菌最常于35 - 45摄氏度的温度范围内被分离出来。然而,少数水样在高达66摄氏度时军团菌检测仍呈阳性(图3)。电导率对军团菌的存在没有影响,pH值(图2)对其存在的影响也很小。铁浓度与军团菌出现频率之间存在正相关(图4)。有机物(图6)和变形虫(表3)似乎也会增加军团菌的出现。由铜制成的管道系统在前五年对军团菌有抑制作用,而在使用时间较长的系统中未检测到这种作用(图5)。

文献AI研究员

20分钟写一篇综述,助力文献阅读效率提升50倍。

立即体验

用中文搜PubMed

大模型驱动的PubMed中文搜索引擎

马上搜索

文档翻译

学术文献翻译模型,支持多种主流文档格式。

立即体验