[医院空调系统新风中微生物的定量监测]

[Quantitative monitoring of microorganisms in incoming air of air conditioning systems in hospitals].

作者信息

Eikmann T, Horning B, Pieler J, Riedel F N

出版信息

Zentralbl Bakteriol Mikrobiol Hyg B. 1984 Mar;179(1):44-55.

PMID:6720148
Abstract

In eight hospitals the quantity of microorganisms in the supply air of air conditioning systems was determined. A Reuter-Centrifugal-Sampler (by Biotest, Frankfurt) sampled 160 litres of air in four minutes and blew the particles with microorganisms on a culture medium (GKA-medium, by Biotest, Frankfurt). The Agar was breeded for 48 hours at 37 degrees C. The colonic-forming-units were counted and transformed to a volume of a cubic meter (CFU/m3). - In other publications you can find determinations of microorganisms in the supply air for operating theatres up to 15 CFU/m3. We found up to 40 CFU/m3 in the supply air after three step filtration (with an high efficiency filter) and 20-85 CFU/m3 after two step filtration. - The recommendations of other authors and some directives say that in the supply air up to 10 CFU/m3 are acceptable. According to our experiences the supply air should not contain more than 10 CFU/m3 after a 3-step-filtration and not more than 50 CFU/m3 after a 2-step-filtration. Otherwise the function of the air conditioning system should be controlled and the maintenance, too. - We think that according to the different requirements in hygiene a supply air with less than 10 CFU/m3 in the mean allows an unlimited use of the air conditioned room, while mean values up to 50 CFU/m3 are acceptable for normal operating rooms and other rooms, except for operating rooms with special hygienic requirements as for example for transplantation, arthroplasty, heart-operations (corresponds to II. and III. classification of rooms, DIN 1946/4). - Values up to 150 CFU/m3 are acceptable for rooms with normal hygienic requirements for supply air (III. classification of rooms, DIN 1946/4) and for labour-, intensive-care, newborn- and infant rooms.

摘要

在八家医院中,对空调系统送风的微生物数量进行了测定。使用Reuter离心采样器(由德国美因河畔法兰克福的Biotest公司生产)在四分钟内采集160升空气,并将带有微生物的颗粒吹到培养基(GKA培养基,由德国美因河畔法兰克福的Biotest公司生产)上。琼脂在37摄氏度下培养48小时。计算菌落形成单位并换算成立方米体积(CFU/m³)。——在其他出版物中,你可以找到手术室送风微生物含量测定结果,高达15 CFU/m³。经过三级过滤(使用高效过滤器)后,我们发现送风微生物含量高达40 CFU/m³,经过两级过滤后为20 - 85 CFU/m³。——其他作者的建议和一些指令规定,送风微生物含量高达10 CFU/m³是可以接受的。根据我们的经验,经过三级过滤后,送风微生物含量不应超过10 CFU/m³,经过两级过滤后不应超过50 CFU/m³。否则,应控制空调系统的功能并进行维护。——我们认为,根据不同的卫生要求,平均微生物含量低于10 CFU/m³的送风可允许无限制地使用空调房间,而对于普通手术室和其他房间,除了有特殊卫生要求的手术室,如移植、关节置换、心脏手术(对应DIN 1946/4标准中的II级和III级房间),平均微生物含量高达50 CFU/m³是可以接受的。——对于送风有正常卫生要求的房间(DIN 1946/4标准中的III级房间)以及产房、重症监护室、新生儿室和婴儿室,微生物含量高达150 CFU/m³是可以接受的。

文献AI研究员

20分钟写一篇综述,助力文献阅读效率提升50倍。

立即体验

用中文搜PubMed

大模型驱动的PubMed中文搜索引擎

马上搜索

文档翻译

学术文献翻译模型,支持多种主流文档格式。

立即体验