Liu Lin, Ma Yong, Huang Ruifeng, Jia Mengyao, Liu Gan, Zheng Weitao
Engineering Research Center of Sports Health Intelligent Equipment of Hubei Province, Wuhan Sports University, Wuhan, 430079, China.
Research Center of Sports Equipment Engineering Technology of Hubei Province, Wuhan Sports University, Wuhan, 430079, China.
Heliyon. 2024 Jul 18;10(15):e34883. doi: 10.1016/j.heliyon.2024.e34883. eCollection 2024 Aug 15.
The indoor thermal environment has a direct impact on human thermal comfort and health. In order to assess the status of the indoor thermal environment of typical sports buildings in hot summer and cold winter climate zones in China, 14 badminton halls in 10 cities in Hubei Province (including 5 venues in Wuhan) in this climate zone are chosen as research objects for field testing of indoor thermal environment parameters in 4 seasons. All the tested stadiums are naturally ventilated in non-event conditions. The results reveal that the average indoor temperature of badminton halls in summer is excessively high (i.e., 31.89 °C), which is higher than the regulation specified in JGJ31-2003 or GB-T18883-2022 on the reference interval of the indoor air temperature of venues in summer, (i.e., (26-28 °C) or (22-28 °C), respectively). The average indoor temperature of badminton halls in winter is too low (i.e., 12.95 °C), and it is lower than the recommendations of JGJ31-2003 or GB-T18883-2022 on the reference interval of the indoor air temperature of venues in winter (i.e., (16-18 °C) or (16-24 °C), respectively), relative humidity and air velocity are in the thermal comfort interval for all seasons, and the indoor thermal environment factors of badminton courts in spring and autumn meet the comfort requirements. The indoor and outdoor temperatures and the relative humidity of badminton courts are highly correlated. The indoor temperature and relative humidity vary according to changes in those factors outdoors, whereas the air velocity is not affected by outdoor changes. In the hot summer and cold winter climate zones, some discrepancies in the indoor temperature variation patterns of badminton halls at various altitudes are detectable. The results of this study aim to provide a solid basis for the development of indoor thermal-comfort standards for sports stadiums in China.
室内热环境直接影响人体的热舒适性和健康。为了评估中国夏热冬冷气候区典型体育建筑的室内热环境状况,选取了该气候区湖北省10个城市的14个羽毛球馆(其中武汉5个场馆)作为研究对象,对其室内热环境参数进行四季实地测试。所有测试场馆在非赛事期间均采用自然通风。结果表明,夏季羽毛球馆室内平均温度过高(即31.89℃),高于JGJ31 - 2003或GB - T18883 - 2022中关于夏季场馆室内空气温度参考区间的规定(分别为(26 - 28℃)或(22 - 28℃))。冬季羽毛球馆室内平均温度过低(即12.95℃),低于JGJ31 - 2003或GB - T18883 - 2022中关于冬季场馆室内空气温度参考区间的建议(分别为(16 - 18℃)或(16 - 24℃)),相对湿度和风速在四季均处于热舒适区间,春秋季羽毛球场地的室内热环境因素满足舒适要求。羽毛球场地的室内外温度和相对湿度高度相关。室内温度和相对湿度随室外这些因素的变化而变化,但风速不受室外变化影响。在夏热冬冷气候区,不同海拔高度的羽毛球馆室内温度变化模式存在一些差异。本研究结果旨在为中国体育场馆室内热舒适标准的制定提供坚实依据。