Abstract

The current application of the carbon dioxide standard ("Kohlensäuremassstab") of 0.1 vol.-% CO2 given by Pettenkofer 140 years ago is assessed in order to evaluate tolerable indoor air and sufficient indoor air ventilation. For this purpose, criteria by Pettenkofer were contrasted by currently valid criteria. It was found that an actual guidance value should be clearly higher than the one given by Pettenkofer. As confirmed by recent measurements this actual guidance value should be around 0.15 vol.-% CO2. By means of a few examples requirements for indoor aeration of living rooms and classrooms are made evident. The corresponding calculations are based on the indoor air guidance value (i.e. actualised value of Pettenkofer) of 0.15 vol.-% CO2 and are based on respiration rates compiled in "Standards of exposure assessment" by the health authorities of the German federal states. The calculated number of complete renewals of air achieved by circulation shows that recent values given by others concerning the permitted indoor self aeration were set too low and require correction. Applying the demonstrated requirements for indoor ventilation many of the well known problems of indoor air can be minimised or even solved.

摘要

为了评估可容忍的室内空气质量和充足的室内通风情况,对140年前佩滕科费尔给出的二氧化碳标准(“碳酸标准”)即0.1体积-% CO₂的当前应用进行了评估。为此,将佩滕科费尔的标准与当前有效的标准进行了对比。结果发现,实际指导值应明显高于佩滕科费尔给出的值。最近的测量证实,这个实际指导值应为0.15体积-% CO₂左右。通过几个例子,说明了对客厅和教室室内通风的要求。相应的计算基于0.15体积-% CO₂的室内空气指导值(即佩滕科费尔的更新值),并基于德国联邦各州卫生当局编制的“暴露评估标准”中的呼吸率。通过循环实现的空气完全更新次数的计算表明,其他人最近给出的关于允许的室内自然通风的值设定得过低,需要修正。应用所证明的室内通风要求,可以将许多众所周知的室内空气问题降至最低甚至解决。

文献检索

告别复杂PubMed语法,用中文像聊天一样搜索,搜遍4000万医学文献。AI智能推荐,让科研检索更轻松。

立即免费搜索

文件翻译

保留排版,准确专业,支持PDF/Word/PPT等文件格式,支持 12+语言互译。

免费翻译文档

深度研究

AI帮你快速写综述,25分钟生成高质量综述,智能提取关键信息,辅助科研写作。

立即免费体验