In hospital water systems legionellae may be resistant to disinfectants in pipework, which is a problem particularly in areas where there is low flow or stagnation of water. We evaluated legionella colonization of a water network of an Italian hospital after time flow taps (TFTs) installation in proximity to dead legs. The water volume flushed was 64 L/day from May 2016, and 192 L/day from December 2016. Before TFTs installation, Legionella pneumophila sg2-14 was detected in all points (4 × 10 ± 3.1 × 10 cfu/L). All sites remained positive (2.9 × 10 ± 1.9 × 10 cfu/L) through November 2016. From December 2016 legionella persisted in one point only (2 × 10 to 6.8 × 10 cfu/L). TFTs with chemical disinfection may reduce legionella colonization associated with dead legs.
在医院的供水系统中,军团菌可能会对管道中的消毒剂产生抗药性,这在水流较小或水停滞的地方是一个特别的问题。我们在意大利一家医院的水网中安装了接近死水段的时间流量龙头(TFT)后,评估了军团菌的定植情况。从 2016 年 5 月开始,每天冲洗 64 升水,从 2016 年 12 月开始,每天冲洗 192 升水。在安装 TFT 之前,所有点位均检测到嗜肺军团菌 sg2-14(4×10±3.1×10cfu/L)。所有点位在 2016 年 11 月之前一直呈阳性(2.9×10±1.9×10cfu/L)。从 2016 年 12 月开始,军团菌仅在一个点位持续存在(2×10 至 6.8×10cfu/L)。带有化学消毒功能的 TFT 可能会减少与死水段相关的军团菌定植。