Airborne endotoxins and humidifier disease.

作者信息

Rylander R, Haglind P

出版信息

Clin Allergy. 1984 Jan;14(1):109-12. doi: 10.1111/j.1365-2222.1984.tb02197.x.

Abstract

The presence of humidifier disease in a printing factory was investigated with particular emphasis on airborne endotoxins. The water in the humidifier was contaminated with Pseudomonas. The amount of airborne endotoxin when the humidifier was operating was 0.13-0.39 microgram/m3. Twenty of the fifty workers investigated reported typical symptoms of fever, chills, and chest tightness when the humidifiers were operating. Symptoms were more frequent among non-smokers. The estimated inhaled dose of endotoxin was found to be sufficient to cause the observed symptoms. The determination of airborne endotoxins in future episodes of humidifier disease is recommended.

摘要

对一家印刷厂加湿器疾病的情况进行了调查,特别关注空气中的内毒素。加湿器中的水被假单胞菌污染。加湿器运行时空气中内毒素的含量为0.13 - 0.39微克/立方米。在接受调查的50名工人中,有20人报告说加湿器运行时出现发烧、寒战和胸闷等典型症状。症状在不吸烟者中更为常见。发现内毒素的估计吸入剂量足以导致观察到的症状。建议在未来加湿器疾病发作时测定空气中的内毒素。